SL Power Electronics GPM41 User Manual

Gpm41 series installation instructions

Advertising
background image

CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
Internet: www.condorpower.com


MODEL NUMBERS: GPM41-X, where X represents the output voltage which may be any number
from 5 thru 28. May be followed by suffix –XXX where XXX may be any number from 001 thru 999 to
indicate value added configurations that have no impact on safety and/or suffix G to indicate compliance
to RoHS.

RATINGS

Input: 100-240 V ac, 1.3 A, 50/60 Hz.
Output: 6 A or 40 W maximum or see table for standard output voltage models.

Model

Output

Watts

GPM41-5

+5 V dc 6.0 A

30

GPM41-12 +12 V dc 3.3 A

40

GPM41-15 +15 V dc 2.7 A

40

GPM41-24 +24 V dc 1.7 A

40

GPM41-28 +28 V dc 1.4 A

40

Notes: 1. Maximum ambient temperature for rated output is 50 ºC.

2. Maximum Relative Humidity 96 %, no condensation.

3. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions

before application of power.

SAFETY COMPLIANCE STANDARDS: All models are Certified to be in compliance with the
applicable requirements of IEC/EN/UL 60601-1, and CAN/CSA 22.2 No. 601.1.

CLASSIFICATION:

(5.1)

Protection against electric shock = Class I

(In accordance with sub-

(5.2)

Degree of protection against electric shock = Signal output or intermediate

clause 5 of IEC 60601-1)

(5.3)

Protection against harmful ingress of water = Ordinary (no protection)

(5.5)

Not suitable for use in the presence of flammable anesthetic mixture

(5.6)

Mode of operation = Continuous

SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole
responsibility that all models listed above are in conformity with the applicable requirements

of EN 60950-1 following the provisions of the Low Voltage Directive 73/23/EEC.

OVERCURRENT PROTECTION: External overcurrent protection must be provided in the end
application. IEC 60601-1 requires that both supply leads (phase and neutral) be protected against
overcurrent. A 2.5 A 250 V rated fuse with an I

2

t rating >20 is recommended. The fuse current rating

must not exceed 2.5 A. The fuses must meet the requirements of IEC 60601-1 and be acceptable for the
country in which the host equipment is to be installed.

WARNING! RISK OF FIRE! A blown fuse is an indication of catastrophic failure of circuit
component(s). Repair must be performed by Condor authorized personnel.

WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring
traces and heatsinks.

41-34227-0001 Rev. F 10/06/05

Page 1 of 2

GPM41 SERIES

INSTALLATION INSTRUCTIONS