SL Power Electronics GSM25 User Manual

Installation instructions gsm25 series

Advertising
background image

CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565

RATINGS

Input: 100-240 V ac, 0.9 A, 50/60 Hz
Outputs:

Model

Watts

1

Output #1

Output #2

Output #3

GSM25A

25

+5.1 V dc 2.5 A

+12 V dc 1.5 A

-12 V dc 0.2 A

GSM25B

25

+5.1 V dc 2.5 A

+15 V dc 1.5 A

-15 V dc 0.2 A

GSM25D

25

+5.1 V dc 2.5 A

+24 V dc 1 A

-12 V dc 0.2 A

GSM25G

25

+3.3 V dc 2.5 A

+12 V dc 1.5 A

-12 V dc 0.2 A

Notes:
1. Maximum continuous output power with Chassis and Cover option is 20 W.
2. Maximum operating ambient is 50 °C.
3. Maximum operating Relative Humidity 96 %, no condensation.
4. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before application of

power.

CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL 2601-1 2

nd

Edition, CSA 22.2 No. 601.1-M90, IEC 601-1 (1988)/EN 60601-1: 1990 +A1 +A2

CLASSIFICATION:

(5.1)

Protection against electric shock = Class I

(In accordance with sub-

(5.2)

Degree of protection against electric shock = Signal output or intermediate

clause 5 of IEC 601-1)

(5.3)

Protection against harmful ingress of water = Ordinary (no protection)

(5.5)

Have not been evaluated for use in the presence of a flammable anaesthetic

mixture with air, oxygen, or nitrous oxide. This evaluation is to be made on the
end equipment by the OEM.

(5.6)

Mode of operation = Continuous

GROUNDING: The Functional Earth terminal must be bonded to Protective Earth in the host
equipment. Using the Functional Earth terminal on the supply for the grounding the host equipment is
not recommended. A separate dedicated grounding point should be used.

OUTPUTS: All output commons should be connected to Protective Earth in the end application. The
output(s) are intended for Protectively Earthed Signal Output and Intermediate Circuits only. The
output(s) are not acceptable for patient connection without additional isolation. All DC outputs are
SELV under normal and single fault conditions.

OVERVOLTAGE PROTECTION: Only output #1 is monitored for an overvoltage condition. The
trip-point for a 5 volt output is 5.6 to 6.8 volts. In some applications where an overvoltage condition
could result in a hazard as defined in applicable safety standards, redundant or additional overvoltage
protection may be required. Consult factory for details.

CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary
circuits. The components providing isolation from primary to secondary cannot be tested while installed
in the power supply without overstressing basic (primary to ground) insulation. All isolating
components are individually 100 % tested at 4800 V ac prior to installation.

41-34616-0001 Rev. C 11/14/01

Page 1 of 2

INSTALLATION INSTRUCTIONS

GSM25 SERIES