SL Power Electronics OV-24 User Manual

Ov-12/24 series installation instructions

Advertising
background image

2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
Internet: www.condorpower.com

VOLTAGE ADJUSTMENT RANGE: 6.2 – 33VDC

ADJUSTMENT PROCEDURE:

1.

REFER TO CHART 1 FOR SUGGESTED OVP TRIGGER VOLTAGES.

2.

CONNECT TEST CIRCUIT AS SHOWN IN FIGURE A. TEST VOLTAGE SOURCE MAY BE ANY
POWER SUPPLY WITH A SHORT CIRCUIT LIMIT OF LESS THAN 8 AMPS (OVP-12) OR 20 AMPS
(OVP-24).

3.

ENERGIZE AND ADJUST THE TEST VOLTAGE SOURCE TO THE DESIRED OVP VOLTAGE.

4.

ROTATE THE OVP ADJUSTMENT POT CCW (FROM ITS MAXIMUM CW POSITON) UNTIL THE OVP
FIRES AS INDICATED BY A BY A 1 VOLT READING ON M1. LEAVE THE POT IN THIS POSITION,
UNIT IS NOW READY FOR INSTALLATION INTO POWER SUPPLY.

5.

BOLT THE OVP ONTO THE POWER SUPPLY USING THE MOUNTING HOLES PROVIDE. CONNECT
THE WHITE (+) LEAD TO THE POSITIVE OUTPUT AND THE BLACK (-) LEAD TO THE NEGATIVE
OUTPUT.



CHART 1




















FIGURE A




















Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other
than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA,
EN, and IEC safety standards.

41-35625-0001 Rev. A 5/4/06

OV-12/24 SERIES

INSTALLATION INSTRUCTIONS

MODEL

INTERMITTENT

CONTINUOUS

OVP-12

12A

8A

OVP-24

30A

20A

POWER SUPPLY

OUTPUT VOLTAGE

SUGGESTED OVP

TRIGGER VOLTAGE

5 VDC

6.2+/-0.4V

6 VDC

7V

12 VDC

14V

15 VDC

17V

18 VDC

21V

20 VDC

23V

24 VDC

27V

DUAL +/-12 VDC

27V

DUAL +/- 15 VDC

33V

CURRENT +
LIMITED
POWER
SUPPLY

-

+
OVP-12
OR
OVP-24
-

M1