Sloan SMO Battery Powered Retrofit User Manual

Side mount operator unit, For urinals & toilets, Installation instructions

Advertising
background image

The Side Mount Operator sends out a continuous infrared beam that is reflected back by the presence of a person in

front of the urinal or toilet. “Object Lock” technology differentiates between someone walking past the unit or actually

using the fixture.

Using the supplied collar wrench,

remove handle from flush valve.
Note: On some flush valves with

a faulty air vent, or recently flushed

valve, be prepared to collect a small

amount of water with a rag or sponge

placed under the handle.
Place collar gasket into collar nut and

attach the Side Mount Operator unit

where the handle was removed. Tighten

collar nut with supplied collar wrench.
Note: Save handle in the event you wish

to reuse for service of Side Mount

Operator.

INSTALLATION

1

Using supplied battery compartment wrench, remove battery

compartment from the Side Mount Operator unit.

Load batteries into compartment tray (note

position of batteries in tray), and reinstall

battery tray into the Side Mount Operator unit.

Secure tray with battery compartment wrench.
The last three turns of the wrench will activate the Side Mount

Operator unit. The Side Mount Operator System is now

operational.
Your Side Mount Operator unit comes preset from the factory. If

special circumstances require adjustment of the activation

distance, see section “Adjusting Your Side Mount Operator.”
The Side Mount Operator unit has a 7 minute start-up sequence in

which the Object Lock Sensor will flash the User-In-View green

LED continuously as long as a user is in view. After the start-up

sequence is completed and when the Object Lock Sensor has a

user in view, the User-In-View green LED will flash only 3 times

after 5 seconds delay. This delay prevents needless flushes when

someone walks by.

-

-

+

+

-

-

+

+

ACTIVATION

VISUAL INDICATOR GUIDE

Use battery compartment wrench

to remove battery compartment

tray.

Remove cover by rotating the cover

up at the end over the battery

compartment and slide out.

Sensor Adjustment Tool comes in a

built in storage pocket. Replace after

use.

ADJUSTING YOUR SIDE MOUNT OPERATOR

Trouble Shooting Guide

PROBLEM

CAUSE

SOLUTION TO PROBLEM

Green LED (light) flashes 3

times when there are no users

Green LED (light) flashes

continuously when Object Lock

Sensor is activated by a user

Yellow LED (light) flashes

Not enough water to fixture or

too much water to fixture

Valve will not operate

Valve does not shut off

Valve does not flush even after

Sensor Range has been adjusted

Front of Object Lock Sensor is covered or

Object Lock Sensor is set too far out,

registering the opposite wall or door as a user

Side Mount Operator unit is in 7 minute start up

mode (when first activated) or Sensor Range

Reset Button has been depressed

Batteries need replacing

Diaphragm damaged or valve control stop

improperly adjusted

Object Lock Sensor range set too close to Side

Mount Operator, batteries are dead, or water

supply is turned off

Dirt or debris preventing diaphragm from

functioning properly

Dead batteries

Remove item covering sensor or adjust Sensor Range

activation distance. (See section “Adjusting Your Side Mount

Operator.”)

Green LED (light) will flash only 3 times

acknowledging a user is in view after the 7 minute

start up mode

Replace batteries

Replace diaphragm and/or adjust valve control stop

Adjust Object Lock Sensor — Replace batteries — Turn

water on.

Remove dirt or debris, consult valve manufacturer’s

directions

Replace batteries

Remove Battery Compartment

Install Battery Compartment

SIDE MOUNT OPERATOR COMPONENTS

INSTALLATION INSTRUCTIONS

Side Mount Operator Unit

for Urinals & Toilets

Restroom Hygiene Through Technology

Manufactured for Sloan Valve Company • 10500 Seymour Avenue • Franklin Park, IL 60131 • Phone: 1-800-9-VALVE-9 or 1-847-671-4300 • Fax: 1-800-447-8329 or 1-847-671-4380

www.sloanvalve.com

0816544 Rev. 2 (09/14)

USER-IN-VIEW LED (Green light flashes 3 times after 5

second delay when a user is in view. The green light

flashes constantly when a user is in view during the

7 minute start up sequence.)

OBJECT LOCK SENSOR

(Detects user or object)

BATTERY LED (Yellow light flashes

indicating it is time to replace

batteries with 4 new “C” batteries)

COURTESY MANUAL FLUSH BUTTON

(Allows manual activation of flush when

needed)

To change activation distance for the Object Lock Sensor:

1

Remove battery compartment tray as shown at left.

2

Remove cover and sensor adjustment tool as shown at left.

3

Replace battery compartment in Side Mount Operator to activate unit.

4

Press sensor range reset button as shown at lower left (the green L.E.D. will flash continuously when it has an

object in view for the seven minute reset period).

5

Stand at desired activation distance.

6

Use sensor adjustment tool and turn Sensor Range Adjustment Screw all the way down (counterclockwise)

and then turn slowly up (clockwise) until green LED begins to flash.

7

Ensure Object Lock Sensor is not detecting stall door or wall by closing door, stepping out of sensor path and

making sure green LED is not flashing. If sensor locks onto door or wall, unit will not flush properly. Shorten

activation distance.

8

Remove battery compartment, replace sensor adjustment tool and cover. Replace battery compartment tray to

reactivate Side Mount Operator unit.

9

After 7 minute start-up sequence, the green LED will flash only 3 times when a user is in view

(after a 5 second delay).

2

Advertising