Super Systems X5 Calibration Manual User Manual

Super Systems Equipment

Advertising
background image

X5 Controller

Calibration Guide

Super Systems Inc. X5 Controller: Calibration Guide. (Document #4615; New: 05/01/2014).

Visit us online at

http://www.supersystems.com

.

Introduction

The instrument calibration is based on a series of steps. Each step performs the calibration of a particular input or

output. It must be done only when strictly necessary and using reference instruments with a high accuracy. Then the

instrument must remain switched on at current environmental conditions for at least one hour.

Calibration Procedure
Starting from operation mode, press and hold both the “

“(enter) and “

“(menu access) keys. “C.PaS” will

appear. Enter the Configuration Password (default: 33).

NOTE: See the X5 Controller product manual section “4.6 PARAMETERIZATION - ACCESS MENU - PASSWORD

- CALIBRATION” for more details on the Configuration Password.

“C.tc” (T/C calibration) will appear on the lower display while a value will appear on the upper display.
Generate a signal using the below table; use copper wire to source the signal. Press the “

“ or “

“ keys to

adjust the value to be as close to zero as possible: 0 ±2.

Step

Function

Action

C.tc.

TC calibration

Apply 50.000mV to the input – set with

or

keys

C.Pt.

RTD calibration

Apply 313.594 Ω to the input – set with

or

keys

C.mV.

mV calibration

Apply 300 mV to the input – set with

or

keys

C.Vol

Volts Calibration

Apply 10 V to the input – set with

or

keys

C.Ma

mA calibration

Apply 20mA to the input – set with

or

keys

C.S. V

Remote Setpoint Volts

calibration

Apply 10 V to the input – set with

or

keys

C.S. mA

Remote Setpoint mA

calibration

Apply 20mA to the input – set with

or

keys

Table 1 - Calibration types and actions

Wait until the displayed value remains stable: 0 ± (2 to 5).


IMPORTANT: Press the “↵” key to bypass a calibration step. DO NOT press the “

“ or “

“keys unless you

want to Calibrate that specific step.


When the calibration is correct, press the “↵” key to go to the next step. It is possible to not modify the
calibration. When the step has been displayed on screen DO NOT press the “

“ or “

“ keys; only press the

“↵” key until out of calibration mode.

–OR-
After “C.tc.”, press the “↵” key to re-enter normal operation.