Thermo Technologies USDT 3000 User Manual

Page 10

Advertising
background image

9

ROUBLESHOOTING

Problem: Nothing happens when unit is powered-up.
Cause/Remedy: The fuse could be blown – check and replace if necessary. If the fuse blows
again, then the pump draws more current than the unit is design to supply. Use an auxiliary relay
or contact your product supplier.

Problem: Operating control red lamp is flashing.
Cause/Remedy: This indicates a system alarm warning, which may be caused by a sensor fault:

Error code –888.8 is displayed

è (TC, TS or TT) sensor cable is short circuited

Error code 888.8 is displayed

è (TC, TS or TT) sensor cable is open

Following table shows the impedance characteristics of PT 1000 sensors:

o

C

- 10

0

10

20

30

40

50

60

70

80

90

100

110

o

F

14

32

50

68

86

104

122

140

158

176

194

212

230

OHM

961 1000 1039 1078 1117 1155 1194 1232 1271 1309 1347 1385 1423




PECIFICATION


Supply Voltage

120 V AC

Fuse

4 A

Phantom Load

max. 2 W

Hysteresis

6 degrees

Delta T

4 – 24

o

F

Overheating Range

100 – 200

o

F

T

S