Thermon Electric Heat Tracing User Manual

Page 10

Advertising
background image

9

Checklist for Self-Regulating and Power-Limiting Heat Tracing

General Information

Project Number:

Installation

Contractor:

Unit Number:

Thermon Reference

Number:

Customer Ref. Number:

Inspector:

Record 1: Prior to Installation

Cable Type:

Reel Number:

Reel Length (M):

Insulation Resistance:

(M Ohms)*

Tested By/Date:

Witnessed By/Date:

Record 2: After Cable Installation

Line Number:

Thermostat Number:

Equipment Number:

Junction Box Number:

Circuit/Heater Number:

Unused Entries

Plugged Off:

Circuit Switch Number:

Heater Length (M):

Metal Sheath Connected

to Earth/Ground:

Insulation Resistance:

(M Ohms)*

Tested By/Date:

Witnessed By/Date:

Record 3: After Thermal Insulation is Installed

Insulation Watertight:

Insulation Resistance:

(M Ohms)*

Tested By/Date:

Witnessed By/Date:

Record 4: Final Commissioning

Panel Number:

Ambient Temp. (°C):

Breaker Number:

Pipe Temp. (°C):

Volts:

Recorded Amps

(after 5 min.):

Tested By/Date:

Witnessed By/Date:

*NOTE: Minimum acceptable insulation resistance should be 20 megohms for Records 1 and 2 and

5 Megohms for Record 3.