Technical Guide

MUA II Controller

11

Space Temperature Sensor

A Space Temperature Sensor is used with the MUA II Controller to
provide for Supply Air Temperature Reset. At a specifi ed Space Tem-
perature Setpoint, the Supply Air Setpoint will be reset towards the
Maximum Supply Air Temperature Setpoint. For more information on
the operation of this sequence, see the Sequence of Operation section of
this manual. This sensor is a 10K Type III thermistor sensor. See Figure
8
for complete sensor wiring details.

Wiring Details

GND

TMP

Space Temperature Sensor

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

MUA II Unit Controller Board

Figure 8: Space Temperature Sensor Wiring