6618-2202

TD-36 – Silent answering on predefined number

The TD-36 is connected to a power meter which is remotely monitored. The TD-36
shares the PSTN line with normal telephones which is preferred not to give a ring signal
when the meter is read.
The TD-36 is configured to answer calls on the Caller ID received, the valid numbers to
answer is programmed into the TD-36. There exists a number of standards for sending
Caller ID check which standard is used by your operator. The TD-36 supports the major
implementations of Caller ID. In this example the DTMF Caller ID version is used.
Note that some implementations doesn’t give the possibility to make a silent answer
since the Caller ID is sent between first and second ring signal.
The modem in the calling end is here chosen to be a PSTN modem, but can be any of
the PSTN, ISDN or GSM modem from Westermo product range.

Configure the TD-36 connected to the power meter

PSTN

Network

AT&F

Set the unit to factory default

AT+IPR=9600

DTE baudrate 9600

AT+ICF=3,4

Character framing 8 data, 1 stop, parity none

ATS0=0

No auto answer on Ring signals

ATQ1E0&C1&K0&A1

Suitable for PLC communication

AT&W

Save settings

AT*WACCTAB=1,”016428000”
AT*WACCTAB=2,”016480250”

Set the valid A-numbers for automatic answering

AT*WCID=3,3

Set Caller ID to A-number answer with DTMF coded numbers