La-01 dc – Westermo LA-01 User Manual

Page 4

Advertising
background image

8

6110-2012

Direction

Pin configuration 10 mA balanced current loop

W1

Channel 1

Channel 2

Channel 3

Description

Receiver

1

1

1

(R+)

Receiver

2

2

2

(R–)

Transmitter

3

3

3

(T+)

Transmitter

4

4

4

(T–)

5

5

5

Shield *

* If shielded cable is used, connect the shield only at one end to avoid ground currents.

10 mA balanced current loop

Transmission range (10 mA balanced current loop)

Cable

Transmission speed bit/s

42 pF/m

600

1 200

2 400

4 800

9 600

19 200

38 400

0.3 mm

2

18 000 m

12 000 m

8 000 m

5 000 m

2 500 m

1 000 m

500 m

LA-01 DC

Specifications

Switch settings

According to LA-01 AC

Power supply

12–36 V DC

Power consumption

Max 3 W

Isolation

1000 V

Fuse F1

1.6 A fast 5x20 mm

All other specifications according to LA-01 AC

Connections

According to LA-01AC, except power supply

Connection no.

Power supply

1

+ Voltage

2

– Voltage

1 2 3

POWER

12-36VDC

CHANNEL 3

CHANNEL 2

CHANNEL 1

Direction

RS232-C/V.24

ITU-T V.24

Description

Circuit no.

I

1

1

1

103

TD/Transmitted Data

O

2

2

2

104

RD/Received Data

O

4

4

4

+12 V (Pull-up resistor)

5

5

5

102

SG/Signal Ground

I = Input, O = Output on LA-01

Connections
RS-232-C/V.24

Channel 1

Channel 2

Channel 3

Advertising