Ratings and safety control drawing – Westermo MDW-45 User Manual

Page 6

Advertising
background image

6

6617-2203

Ratings and safety control drawing

Power

12 – 48 VDC; 95 mA

Ambient temperature

–40ºC ≤ Ta ≤ +70ºC

Maximum surface temperatur 136 ºC (temperatur class T3)

Degree of protection

IP21

Installation spacing

Minimum 25 mm above / below and minimum 10 mm left / right

RS-232

Position Direction* / description

Input /Output values

1

Not connected

U

max

= ± 12 Vpk

I

max

= ± 60 mA

Data rate:
1.2 – 115.2 kbit/s

2

Out / Received Data (RD)

3

In / Transmitted Data (TD)

4

Not connected

5

– / Signal Ground (SG)

6

Out / Data Set Ready (DSR)

7

In / Request To Send (RTS)

8

Out / Clear To Send (CTS)

9

Not connected

RS-422/485

Position Direction* / description

Input /Output values

1

In / R+ line RS-422

U

max

= ± 5 Vpk

I

max

= ± 250 mA

Data rate:
1.2 – 115.2 kbit/s

2

In / R– line RS-422

3

In / Out / T+ line RS-422/485

4

In / Out / T– line RS-422/485

Power – LV

Position

Direction* /
description

Intput values

1

In / COM

U

in

= 9.6 – 57.6 VDC

Max

in

= 0.16 A @ 9.6 VDC

P

In

= 2 W

2

In / +VA

3

In / +Voltage B

4

In / Common

Galvanically isolated via power transformer and optocoupler.
Capacitively isolated via Y1 capacitor rated 440 Vrms 3300 pF.

Advertising