Model

Ei146 Optical

Installation & Placement

Wiring for Interconnected Alarms

Be very careful about correctly wiring the alarms as mixing Live and Neutral
will blow/damage interconnected alarms.

Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector

Please consult instruction booklet for specific installation details

Important Precaution:

Do not install the actual smoke/heat alarm
itself in new or renovated buildings until all
work is completed (including floor coverings)
and the building has been fully cleaned. The
wiring can be installed when appropriate.
(Excessive dust and debris from building work
can contaminate the smoke chamber and
cause problems, and it will also invalidate the
guarantee). If it must be installed, cover it
completely, particularly around the edges, with
a dust cover (eg. a plastic bag), until all
cleaning is finished.. Connect wires to the unit
as in wiring diagram. All wiring must comply
with local codes.

Technical Specification

Sensor

Optical, uses light scatter from
smoke


Sensitivity:

Complies with BS 5446 Part 1:
2000


Source:

Contains no radioactive material


Airspeed:

Essentially immune to the effect

of airspeed.


Button Test:

Simulates the effect of smoke and
checks chamber, electronics and
horn.


Ambient Light:

Chamber housing design and
compensation overcomes
problems with stray light.


AutomaticSelf-Test:

Smoke Chamber is tested every 40

Sec. and unit beeps (without LED

flash) if it is degraded.


Insect Screen:

Prevents insects or debris entering
chamber (1.00mm mesh size)


Supply Voltage:

230V AC


Battery back up:

9V Alkaline Battery


Specifications are subject to change


Power-On Indicator:

Continuous green LED


Alarm:

Electronic Piezoelectric horn


Alarm Sound Output:

85dB (minimum) at 3m


Alarm Status:

Red LED flashes every second on

unit sensing fire


Temperature Range:

0° to 40°C


Humidity Range:

15% to 95% Relative Humidity


Interconnect:

Up to 12 interconnected mains
powered easi-fit smoke or heat
alarms, along with an EI128 relay
base


Fixing:

Easi-Fit mounting base


Plastic material:

UL94VO flame retardant


Dimensions:

152mm x 50mm depth


Weight:

345g


Warranty:

5 year (limited) warranty


Approvals:

Kitemarked to BS EN 14604:2005,
CE Approved