Section 2: Rear Mounted

Connections

When making bolted connec-

tions to the equipment or to the

adapters themselves, all which

have pre-tapped holes, it is

important not to exceed the rec-

ommended torque values. In

addtion, any connection hard-

ware used should be the exact

length required and not extend

out past the mounting hole.

Failure to follow these require-

ments could result in equipment

damage and/or failure.

It is recommended that appropriate

interphase barriers be installed

between inside and outside primary

terminals with all rear connected

configurations to insure insulation

integrity. If interphase barriers are

ordered from Eaton, installation

instructions are provided with the

barriers (IL01301021E).

Straight Bus Adapter
Proceed with the following 3 steps:
Step 1: Bolt a straight bus adapter

to the vertically positioned mounting

holes of a primary terminal pad as

shown using the hardware provided.

Torque the bolted connection to 120

in-lbs (13.6 N-m) using a torque

wrench.

Step 2: Complete all six adapter

connections (eight for 4-pole) in a

similar fashion with the three line

adapters pointing up and the three

load adapters pointing down as

shown.

Step 3: Reverse the procedure just

described to remove the adapters.

Figure 4 Typical Cable Adapters

MCM Sizes

(CU/AL )

400
500

Step 1

Step 2