1 –Pump 9-Station Controller

Chapter 3: Installation

26 of 38

System Setup
To set the system settings and features of your conveying system, press the F6 key on the
controller keypad while in the Main Menu screen. The initial (of three) System Setup screen
will be shown (below):

Figure 13: Initial System Setup Screen

This screen will allow you to set the following features:

• INSTALLED HOPPERS – This will allow you to input the number of stations present

in the system. Values can be entered between 0 and 9 total hoppers.

• HI VAC DEBOUNCE- This is the minimum amount of time (in seconds) that a High

Vacuum Signal will occur before being recognized by the system. This value can be
entered between 0.1 and 9.9.

• HI VAC DELAY- This is the amount of time (in seconds) before the High Vacuum

Alarm will occur once a High Vacuum Signal has been recognized. This value can be
set between 2.0 and 9.9.

Once the values have been entered for the settings listed above, the operator can choose to do
the following:

• Turn the system On or Off (Press F1 while in this screen)
• Enter additional values for the system in the second setup screen (Press F3).
• Return to the Main Menu (Press F6).