Motor electrical data, Motor/drive weight data, Eight and – Enviro LCD MONITOR 170S5FG User Manual

Page 13: Lectrical

Advertising
background image

W

EIGHT AND

E

LECTRICAL

D

ATA

• MQL

13

Motor Electrical Data

NOTES:

1. Actual motor nameplate AMPs may vary, but will not exceed values shown.

2. Consult factory for applications requiring special motors.

115/1

208/1

230/1

277/1

208/3

230/3

460/3

575/3

1/3

6.3

3.5

3.2

2.6

1.7

1.5

0.8

-

1/2

7.8

4.3

3.9

3.6

2.2

2.1

1.1

0.9

3/4

10.6

5.4

5.3

5.0

3.2

3.0

1.5

1.2

1

15.0

8.3

7.5

5.5

4.0

3.6

1.8

1.4

1 1/2

-

-

-

-

5.3

5.0

2.5

1.9

2

-

-

-

-

7.0

6.4

3.2

2.5

3

-

-

-

-

9.1

9.0

4.5

3.2

5

-

-

-

-

14.2

12.8

6.4

5.2

7 1/2

-

-

-

-

22.2

21.6

10.8

8.2

10

-

-

-

-

28.6

28.4

14.2

11.4

15

-

-

-

-

44.9

40.6

20.3

16.2

MAXIMUM MOTOR AMPERAGE

HORSEPOWER

VOLTAGE

Motor/Drive Weight Data

1/3

1/2

3/4

1

1 1/2

2

3

5

7 1/2

10

15

ODP

25 [11]

28 [13]

30 [762]

35 [16]

45 [20]

35 [16]

75 [34]

100 [45]

125 [57]

125 [57]

220 [100]

TEFC

28 [13]

35 [16]

33 [338]

45 [20]

65 [29]

70 [32]

85 [39]

105 [48]

145 [66]

160 [73]

295 [134]

E+

N/A

N/A

N/A

40 [18]

55 [25]

55 [25]

90 [41]

100 [45]

145 [66]

130 [59]

300 [136]

2 SPEED

45 [20]

35 [16]

33 [338]

45 [20]

40 [18]

70 [32]

75 [34]

N/A

N/A

N/A

N/A

MOTOR WEIGHTS

MOTOR HORSEPOWER

MOTOR TYPE

NOTES:

1. Includes motor, pulleys, belts, and motor base.

2. Motor/drive weight data is shipping weight in pounds [kilograms].

General Fan Notes

Forward Curved Fans (Belt Drive)

1. Consult factory for applications at operating conditions not in the following table and curves.

2. Fan motor voltage, fan rotation, and fan RPM may require field setting/adjustment.

3. Drive losses not included in fan performance table and curves.

4. In direction of airflow, after fan discharge – only LPM (Large Plenum) and EHB (Electric Heat Blow Thru) are available.

5. Section will have internal isolation.

Plug Fans (Direct Drive)

1. Consult factory for applications at operating conditions not in the following table and curves.

2. VFD's are recommended for operation and field balancing of units whether factory supplied and factory mounted, field

supplied and factory mounted, or field supplied and field mounted.

3. In direction of airflow, there must be space prior to the plug fan inlet. For sizes 02 through 06, the minimum requirement

is either an SAM (Small Access) or an MCM (Medium Coil). For sizes 08 through 17, the minimum requirement is an MAM

(Medium Access).

4. Section will have internal isolation.

ENVIRO-TEC