Specifications – Emerson Liebert Surge and Signal Protection User Manual

Page 4

Advertising
background image

Emerson Network Power.

The global leader in enabling Business-Critical Continuity.

EmersonNetworkPower.com

AC Power Systems

Connectivity

DC Power Systems

Embedded Power

Integrated Cabinet Solutions

Outside Plant

Power Switching & Controls

Precision Cooling

Site Monitoring

Surge & Signal Protection

Services

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

Technical Support

800 288 6169 Toll-Free

607 724 2484 Phone

607 722 8713 Fax

Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.

Specifications

While every precaution has been taken to ensure accuracy and

completeness in this literature, Liebert Corporation assumes no

responsibility, and disclaims all liability for damages resulting

from use of this information or for any errors or omissions.

© 2005 Liebert Corporation. All rights reserved throughout

the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks

of their respective owners.

® Liebert and the Liebert logo are registered trademarks

of the Liebert Corporation.

SL-22060 (R3/06) Printed in USA

Connection Means

Parallel Connected

Agency Listing

UL 1449 Listed (Second Edition), UL 1283, CUL

Protection Modes

All modes standard (L-N, L-G, N-G, L-L); Optional – any combination

Surge Current Capacity

250 to 750kAmps per phase depending on model

Primary Stage Joule

H1 Models – 250 Joules

Rating (L-N) per phase

H2 Models – 500 Joules

EMI/RFI Filtering

41 dB at 100 KHz, 31 dB at 1 MHz, 35 dB at 10 MHz, 53 dB at 100 MHz

Response Time

Picosecond range

Repetitive Surge

15,000 - 120,000 10kA Category C3 surges per phase depending on model

Enclosure

NEMA 12 standard Optional - NEMA 3R, 4, 4X and caseless

Line Frequency

47-63 Hertz

Line Voltage

+/-15% nominal

Temperature

- 40 to +60 degrees C

Relative Humidity

0 to 95% noncondensing

Altitude

0 to 18,000 feet

Audible noise

Less than 45 dBa

Warranty

10-years parts, 5-year labor

Standard Features

Unit status indicators, Dual, isolated form C dry contacts

Optional Features

Integral disconnect, Audible alarm, Transient counter – single or dual