7

Operating Instructions and Owner’s Manual

Enerco | Compact Unit Heater

5.

Vent termination must be a minimum of 4' (1.2m) below or 4’

(1.2m) horizontally from any soffit vent or under-eave vent.

6.

Vent must be a minimum of 6' from an inside corner formed

by two exterior walls. If possible, leave a 10' clearance.

7.

Vent termination must be a minimum of 10' (3m) from any

forced air inlet (includes fresh air inlet for other appliances,
such as a dryer).

8.

When termination is routed through an exterior combustible

wall the vent must be supported using a listed clearance
thimble. Where local authorities permit, a single section of
type B-1 vent pipe may be used as an alternative to the
thimble. When using a type B-1 vent termination use the
clearances specified by the vent manufacturer. Seal the
connection between the single wall and double wall pipes and
the annular space of the double wall pipe as shown in figure
2. Inside edge of vent termination tee must be at least 12
inches from outside wall as shown in figure 3 .

9.

For horizontal venting, the vent pipe shall be supported with

hangers no more than 3ft. (1m) apart to prevent movement
after installation.

D – HORIZONTAL VENTING – COMMERCIAL

1.

Horizontal commercial installations are for buildings which are

not attached to living spaces. The vent may be single wall
vent material installed according to the sections

Venting A - General Recommendations and Requirements

and C - Horizontal Venting General and

D - Horizontal Venting - Commercial. Refer to figure 3.

2.

The vent pipe diameter for horizontal commercial

installations shall be 4" (101mm) on the 45 and 75units. In all

cases a flue transition piece (supplied) is required to fit over

the outlet of the induced draft assembly on the appliance.

3.

Refer to table 2 for maximum vent connector lengths.

4.

Select a wall termination point that will maintain ¼” rise per

foot slope of horizontal run of vent pipe. The vent may be
single wall material minimum 26 GSG (0.46mm) galvanized
steel or equivalent grade stainless steel. Seal single wall vent
material according to the section A - General
Recommendations and Requirements.

5.

For upward sloped vent a condensate tee and drain must be

installed within the first 5’ (1.5m) from the unit heater to
protect the appliance. If a flexible condensate drain line is
used, the drain line must include a loop entering the structure.
If the unit is shut down for an extended period of time and
will be exposed to sub-freezing temperatures, the condensate
may freeze.

E – HORIZONTAL VENTING – RESIDENTIAL

1.

For horizontal residential installations these units are certified

as Category I appliances. The vent may be single wall
material minimum 25 GSG (0.46mm) galvanized steel or
equivalent grade stainless steel. Venting A - General
Recommendations and Requirements
and C - Horizontal
Venting General
and E - Horizontal Venting - Residential.
Refer to figure 6 .

2.

The vent pipe diameter for horizontal residential installations

shall be 4" (101mm) on both 45 and 75 units. A standard vent
transition is required at unit in addition to the transition
supplied with the unit.

3.

The maximum vent length is 5’ (1.5m) plus one 90-degree

elbow.

4.

The vent must maintain a ¼” rise per foot of slope upwards

toward the termination.

FIGURE 3

COMMON VENTING NOT ALLOWED WHEN HORIZONTALLY VENTING THE UNIT HEATER

CONDENSATE DRAIN THROUGH TEE PIPE AND DRAIN LOOP

UPWARD SLOPE ON HORIZONTAL VENT-COMMERCIAL INSTALLATION

MAY BE SINGLE WALL (26 GSG) GALV. OR EQUIV. STAINLESS STEEL SEALED ACCORDING TO

THESE INSTALLATION INSTRUCITONS. SLOPE: + 1/4 INCH FOR 1 FOOT RUN MINUMUM.

INDUCED DRAFT BLOWER

DRAIN LOOP WITH WATER

TRAP (TO CONDENSATE DRAIN)

LISTED THIMBLE

THROUGH COMBUSTIBLE

WALL

12 INCHES MIN.

(30.5 CM)

VENT TERMINATION

CAP

NOTE - MINIMUM HORIZONTAL LENGHT 3 FT. (914MM),
NOT INCLUDING CAP FOR TERMINATION. REFER TO
TABLE 2 FOR MAXIMUM LENGTH AND NUMBER OF
ELBOWS.

12” (30.5 CM)

MINIMUM ABOVE ALL

HIGHEST SNOWFALL

FLUE TRANSITION

(PROVIDED)