Minimum software required, Leds, Minimum software required leds – Extreme Networks BlackDiamond 12804 User Manual

Page 31

Advertising
background image

Extreme Networks 1200 W DC PSU

BlackDiamond 12800 Series Switches Hardware Installation Guide

31

NOTE

Extreme Networks does not recommended installing the 1200 W DC PSU with any AC PSU in the same
BlackDiamond 12804 system. Extreme Networks recommends that DC and AC PSU units not be used together in
the same BlackDiamond switch.

For central DC power connections, the 1200 W DC PSU is intended to be installed only in restricted access
locations (dedicated equipment rooms, equipment closets, or the like) in accordance with Articles 110-16, 110-17,
and 110-18 of the National Electric Code, ANSI/NFPA-70.

WARNING!

Field operators must not attempt to open the 1200 W DC PSU enclosure for any reason; the PSU does not contain
user-serviceable parts. In the event of failure, return the defective 1200 W DC PSU to Extreme Networks for repair
or replacement.

Minimum Software Required

You must be running ExtremeWare XOS version 11.3 or later for the system to recognize the DC PSU.

LEDs

The front panel of the 1200 W DC PSU provides status LEDs.

Table 10

identifies the symbols and

describes the LED activity.

Table 10: LEDs on the 1200 W DC PSU

PSU Condition

Power
Green

Predictive Fail
Amber

Fail
Amber

Power supply DC outputs working normally

On

Off

Off

DC input power present/standby output on

Blinking

Off

Off

Current limit on 48 VDC output

On

Off

Blinking

Predictive failure

On

Blinking

Off

No input power to this PSU only

Off

Off

On

No input power to any PSU

Off

Off

Off

Power supply failure

Off

Off

On