Evaluating and Meeting Cable Requirements

BlackDiamond 12800 Series Switches Hardware Installation Guide

51

cable and maintain an adequate bend radius at all cable turns, particularly where the cable connects to the I/O
module.

Figure 24: Bend Radius for Fiber Optic Cable

Cable Distances

Table 14

shows cable media types and maximum distances that support reliable transmission in

accordance with international standards except where noted.

*

Proprietary to Extreme Networks. Connections between two Extreme Networks 1000BASE-LX interfaces that use 10/125 μm
single-mode fiber can use a maximum distance of 10,000 meters.

Table 14: Media Types and Maximum Distances

Standard

Media Type

Mhz•Km
Rating

Maximum Distance
(Meters)

1000BASE-SX
(850 nm optical
window)

50/125 μm multimode fiber

50/125 μm multimode fiber

62.5/125 μm multimode fiber

62.5/125 μm multimode fiber

400

500

160

200

500

550

220

275

1000BASE-LX
(1300 nm optical
window)

50/125 μm multimode fiber

50/125 μm multimode fiber

62.5/125 μm multimode fiber

10/125 μm single-mode fiber

10/125 μm single-mode fiber*

400

500

500

550

550

550

5,000

10,000

1000BASE-LX70
(1550 nm optical
window)

10/125 μm single-mode fiber

70,000

1000BASE-T

100BASE-TX

10BASE-T

Category 5 and higher UTP cable

Category 5 and higher UTP cable

Category 3 and higher UTP cable

100

100

100

SPG_002

Minimum

2-in. (5.08-cm)

radius

in 90∞ bend

90∞

Optical fiber cable

Advertising