BlackDiamond 12800 Series Switches Hardware Installation Guide

54

For power specifications of the BlackDiamond 12800 series switches, see

Appendix B, “Technical

Specifications.”

AC Power Cable Requirements

Use an AC power cable appropriate for your country. Check your local electrical codes and regulatory
agencies for power cable requirements. The countries listed in

Table 15

have additional requirements as

listed in the table.

NOTE

When using dual power supplies, make sure that each AC power supply attaches to an independent power source.

Replacing the Power Cable

If the power cable plug is unsuitable and must be replaced, connect the power supply wires for the
switch according to the following scheme:

Brown wire to the Live (Line) plug terminal, which may be marked with the letter “L” or colored
red.

Blue wire to the Neutral plug terminal, which may be marked with the letter “N” or colored black.

Yellow/Green wire to the Ground plug terminal, which may be marked with the letter “E” (the
Earth symbol) or colored yellow/green.

Uninterruptible Power Supply Requirements

An uninterruptible power supply (UPS) is a device that sits between a power supply (such as a wall
outlet) and a device (such as a switch) to prevent outages, sags, surges, and bad harmonics from
adversely affecting the performance of the device.

A UPS traditionally can perform the following functions:

Absorb relatively small power surges.

Smooth out noisy power sources.

Continue to provide power to equipment during line sags.

Table 15: AC Power Cable Requirements

Country

Requirements

USA and Canada

• The cable set must be UL-approved and CSA-certified.

• The minimum specification for the flexible cable is No. 18

AWG (1.5 mm

2

), Type SVT or SJT, 3-conductor.

• The cable set must have a rated current capacity of at least the amount rated for each

specific product.

• The attachment plug must be either an Earth-grounding type with a NEMA 5-15P (10

A, 110 V) configuration or a NEMA L6-15P (10 A, 208/240 V)

Denmark

The supply plug must comply with section 107-2-D1, standard DK2-1a or DK2-5a.

Switzerland

The supply plug must comply with SEV/ASE 1011.

Argentina

The supply plug must comply with Argentinian standards.