Sunny Central 800CP XT

DC Input

Maximum DC Power

898 kW

Minimum input voltage / maximum input voltage

500 V to 1,000 V

Minimum MPP voltage

530 V

MPP voltage range at +25 C

641 V to 850 V

MPP voltage range at +50 C

583 V to 850 V

MPP voltage range at +25°C and 60 Hz

641 V to 850 V

MPP voltage range at +50°C and 60 Hz

583 V to 850 V

Rated input voltage

641 V

Maximum input current

1,400 A

Maximum short-circuit current

2,500 A

Maximum reverse current

2,300 A

Number of independent MPP inputs

1

Number of DC inputs

9

AC Output

Rated power at +25°C

880 kVA

Rated power at +50°C

800 kVA

Nominal AC voltage

360 V

Nominal AC voltage range

324 V to 414 V

AC power frequency

50 Hz / 60 Hz

AC power frequency range

47 Hz to 63 Hz

Rated frequency

50 Hz

Rated grid voltage

360 V

Maximum total harmonic distortion

0.03

Maximum AC current

1,411 A

Maximum residual current at the AC output

3,500 A

Maximum overcurrent protection at output

50,000 A

Power factor at rated power

1

Displacement power factor cos φ

0.9 overexcited to 0.9 underexcited

Feed-in phases

3