SMA SSM8-21-BS User Manual
Page 52
12 Technical Data
SMA Solar Technology AG
52
SSMxx-21-IA-BS-JP-en-20
Installation Manual
Electrical Data
PV array
Negatively grounded/positively grounded/isolated
Maximum DC input voltage
1,000 V
DC
Maximum DC output current for SSM8-21-BS/SSM8-21-BS-JP
200 A
DC
Maximum DC output current for SSM16-21-BS/
SSM16-21-BS-JP
280 A
DC
Maximum reverse current
15 kA
DC
Fuse characteristics
gPV
Nominal current strength of string fuses
6 A
DC
/8 A
DC
/10 A
DC
/12 A
DC
/15 A
DC
/20 A
DC
/
25 A
DC
/30 A
DC
Dimensions of string fuses
10 x 38 mm
Maximum current per fuse at maximum current of 25 A
DC
per
measuring channel, maximum output current of 200 A
DC
/
280 A
DC
and ambient temperature of 40°C
0.60 x I
nom fuse
Maximum current per fuse at maximum current of 25 A
DC
per
measuring channel, maximum output current of 200 A
DC
/
280 A
DC
and ambient temperature of 50°C
0.55 x I
nom fuse
Maximum current per measuring input
25 A
DC
Number of string inputs per potential SSM8-21-BS/
SSM8-21-BS-JP
16
Number of string inputs per potential SSM16-21-BS/
SSM16-21-BS-JP
32
Number of string fuses per potential SSM8-21-BS/
SSM8-21-BS-JP
16
Number of string fuses per potential SSM16-21-BS/
SSM16-21-BS-JP
32
Number of measuring inputs per potential SSM8-21-BS/
SSM8-21-BS-JP
8
Number of measuring inputs per potential SSM16-21-BS/
SSM16-21-BS-JP
16
External DC supply voltage*
* via the data cable for RS 485 communication
35 V
DC
to 55 V
DC
DC load-break switch
280 A
DC
Surge arrester for DC input
Type 2
Surge arrester for RS485 communication SSM8-21-BS-JP/
SSM16-21-BS-JP
Type 2
Overvoltage category
II
DC Main Connection to Busbar
Connection to busbar
Ring terminal lugs for M12 screw
Maximum conductor cross-section
300 mm
2
Cable gland
M40