SMA SSM8-21-BS User Manual

Page 52

Advertising
background image

12  Technical Data

SMA Solar Technology AG

52

SSMxx-21-IA-BS-JP-en-20

Installation Manual

Electrical Data
PV array

Negatively grounded/positively grounded/isolated

Maximum DC input voltage

1,000 V

DC

Maximum DC output current for SSM8-21-BS/SSM8-21-BS-JP

200 A

DC

Maximum DC output current for SSM16-21-BS/

SSM16-21-BS-JP

280 A

DC

Maximum reverse current

15 kA

DC

Fuse characteristics

gPV

Nominal current strength of string fuses

6 A

DC

/8 A

DC

/10 A

DC

/12 A

DC

/15 A

DC

/20 A

DC

/

25 A

DC

/30 A

DC

Dimensions of string fuses

10 x 38 mm

Maximum current per fuse at maximum current of 25 A

DC

per

measuring channel, maximum output current of 200 A

DC

/

280 A

DC

and ambient temperature of 40°C

0.60 x I

nom fuse

Maximum current per fuse at maximum current of 25 A

DC

per

measuring channel, maximum output current of 200 A

DC

/

280 A

DC

and ambient temperature of 50°C

0.55 x I

nom fuse

Maximum current per measuring input

25 A

DC

Number of string inputs per potential SSM8-21-BS/

SSM8-21-BS-JP

16

Number of string inputs per potential SSM16-21-BS/

SSM16-21-BS-JP

32

Number of string fuses per potential SSM8-21-BS/

SSM8-21-BS-JP

16

Number of string fuses per potential SSM16-21-BS/

SSM16-21-BS-JP

32

Number of measuring inputs per potential SSM8-21-BS/

SSM8-21-BS-JP

8

Number of measuring inputs per potential SSM16-21-BS/

SSM16-21-BS-JP

16

External DC supply voltage*

* via the data cable for RS 485 communication

35 V

DC

to 55 V

DC

DC load-break switch

280 A

DC

Surge arrester for DC input

Type 2

Surge arrester for RS485 communication SSM8-21-BS-JP/

SSM16-21-BS-JP

Type 2

Overvoltage category

II

DC Main Connection to Busbar
Connection to busbar

Ring terminal lugs for M12 screw

Maximum conductor cross-section

300 mm

2

Cable gland

M40

Advertising
This manual is related to the following products: