6  Preparation for Installation

SMA America, LLC

34

SCCP-US-IA-US_en-41

Installation Manual

Air quality classification for mechanically active substances

Air quality classification for chemically active substances

Ambient conditions for stationary application

Class 4S2

a) Sand in air [mg/m

3

]

300

b) Dust (suspended matter) [mg/m

3

]

5.0

c) Dust (precipitation) [mg/m

3

]

20

Installation sites where appropriate measures are taken to keep dust levels to a minimum.

x

Installation sites where no special measures have been taken to reduce the sand or dust levels and

which are not located in the vicinity of sand or dust sources.

x

Ambient conditions for stationary application

Class 4C2

Mean value

Threshold

a) Sea salt

Occurrence of salt spray

b) Sulfur dioxide [mg/m

3

]

0.3

1.0

c) Hydrogen sulfide [mg/m

3

]

0.1

0.5

d) Chlorine [mg/m

3

]

0.1

0.3

e) Hydrogen chloride [mg/m

3

]

0.1

0.5

f) Hydrogen fluoride [mg/m

3

]

0.01

0.03

g) Ammonia [mg/m

3

]

1.0

3.0

h) Ozone [mg/m

3

]

0.05

0.1

i) Nitrogen oxides [mg/m

3

]

0.5

1.0

Installation sites in rural or densely populated areas with little industry and moderate

traffic volume.

x

Installation sites in densely populated areas with industry and high traffic volume.

x