5 transformer compact station 1250sc, Transformer compact station 1250sc – SMA TCS 500-SC User Manual

Page 35

Advertising
background image

SMA Solar Technology AG

9 Technical Data

Installation Manual

TCS-IT-IEN103610

35

9.5 Transformer Compact Station 1250SC

Medium-voltage side

Low-Voltage Side

Dimensions and Weight

Climatic Conditions

Rated power (@ 25°C)

P

ACnom

1 375 kVA

AC nominal power (@ 45°C)

P

AC

1 250 kVA

AC nominal voltage

V

ACnom

15 kV / 20 kV

AC voltage range

V

AC

13.5 kV … 16.5 kV / 18 kV … 22 kV

Rated grid voltage

V

AC

20 kV

Rated grid frequency

f

AC

50 Hz

Nominal current

I

nom

36.4 A

Nominal input voltage

V

AC

315 V

Nominal input current

I

nom

2 x 1 155 A

Width x height x depth
with medium-voltage switchgear

3 280 mm x 2 550 mm x 2 500 mm

Width x height x depth
without medium-voltage switchgear

2 380 mm x 2 550 mm x 2 500 mm

Weight with medium-voltage switchgear

16.8 t

Weight without medium-voltage switchgear

12.4 t

Degree of protection

*

As per EN 60529

IP23

Operation temperature range

− 20°C … +45°C

Relative humidity, non-condensing

15% … 95%

Maximum operating altitude above sea level
(MSL)

1 000 m

Advertising