5 electrical connection, Electrical connection – SMA TEMPSENSOR-AMBIENT User Manual

Page 8

Advertising
background image

Electrical Connection

SMA Solar Technology AG

8

TempsensorAmb-IEN110610

Installation Guide

5 Electrical Connection

Cabling Recommendations

The cable length and quality have an effect on the signal quality. To achieve a good quality signal,
observe the following instructions regarding cabling:
Outdoors
For the outdoors, use a cable with the following key properties:

• Cross-section: at minimum 4 x 0.25 mm

2

, at minimum 4 x AWG 24

• Outer cable diameter: at minimum 4.5 mm, at maximum 7 mm
• UV-resistant

SMA Solar Technology AG recommends the following cable types:

• Lappkabel: UNITRONIC S-LifY11Y 4 x 0.34 mm

2

• Lappkabel UL-listed: UNITRONIC S-LifY11Y 4 x 0.34 mm

2

Indoors
It is permitted to use non-UV-resistant cables outdoors that are protected by a UV-resistant cable
channel if the cables comply with aforementioned specifications.
SMA Solar Technology AG recommends the following cable types:

• Lappkabel: Unitronic LiYY 4 x 0.5 mm

2

• Lappkabel UL-listed: UNITRONIC LiYY UL/CSA 4 x AWG22/7
• Helukabel: TRONIC LiYY 4 x 0.5 mm

2

4-wire system
To offset measuring errors that occur due to
cable resistance, connect the temperature
sensor via a 4-wire system. This type of
connection ensures the current feed and voltage
measurement are performed by separate pair cables. The length of the cable must not
exceed 30 m.

NOTICE
Damage to Ambient Temperature Sensor due to ingress of fluids

Use only cables with a minimum diameter of 4.5 mm

2

to connect the Ambient Temperature

Sensor. This prevents the Ambient Temperature Sensor from being damaged by any ingress
of fluids (e.g. by rain or snow).

Advertising