Technical Data
Installation Guide
AS-BOX-XL-IEN094410
47
Feed-in meter connection
Consumption meter connection
Battery Connection
Sunny Backup connection
Nominal current
3 x 160 A
Nominal power
110 kW
Maximum torque
6 Nm … 12 Nm
Maximum cable cross section suitable for connection
70 mm²
Fuse
none
Nominal current
3 x 160 A
Nominal power
110 kW
Maximum torque
6 Nm … 12 Nm
Maximum cable cross section suitable for connection
70 mm²
Fuse
none
Voltage
48 V
Maximum cable cross section suitable for connection
2.5 mm²
Maximum power consumption at U
Batmin
800 W
Number
6 / 9 / 12
Nominal current
3 x 43.4 A / 3 x 65.1 A / 3 x 86.8 A
Nominal power
30 kW / 45 kW / 60 kW
Maximum cable cross section suitable for connection
16 mm²
Fuses
12 x 32A line circuit breakers
(tripping characteristic C)