4.4 Mounting the inverter with a top hat rail

Requirements for installing the top hat rail

• Use a TH-35-7.5 supporting rail compliant with DIN EN 60715.
• Use stainless steel top hat rail and screws to prevent contact corrosion.
• Install on level ground only.
• Use fastening material suitable for the surface. Please observe the weight of the inverter.

Procedure

1. Use the top hat rail as a drilling template and mark the positions of the drill holes.
2. Attach the top-hat rail using appropriate screws

(diameter min. 6 mm) and washers (outer diameter
min. 18 mm).
Secure one screw at least every 300 mm.

3. Transport the inverter using the grip recesses on the

sides.

4. Suspend the inverter on the top hat rail using the

opening on its rear wall.