Commissioning

Installation Guide

SC20_25_35-IEN094521

77

Checking the Internal AC Power Supply

• Measure and record AC voltages

– L1-L2
– L1-L3
– L2-L3
– L1-N
– L2-N
– L3-N

Checking DC Voltages

• Measure and record the DC voltage for every input.
• Check that the polarity of each input is correct.
• Check the correct polarity of the DC busbar in the Sunny Central.
• Measure the voltage for every input and every pole to ground.

– If the value is stable, a short to ground is present.

• Measure and compare the voltages of the individual inputs. The voltages must be

approximately equal.

• The voltage must not exceed the maximum DC voltage of the inverter.

WARNING!
Danger of arcing if the measuring device is incorrectly connected.

• Ensure that the measuring device is connected correctly.
• Select the appropriate measuring range.

NOTICE!
Damage to the Sunny Central via excessive DC voltages

The DC voltage of the photovoltaic generator must never exceed the maximum permissible
inverter voltage.

• U

PV

= 1000 V for Sunny Central standard / HE with the EVR option

• U

PV

= 880 V for Sunny Central standard / HE