12.1.3 Grid Support

HzCtlllLim

*

Threshold value for
underfrequency
level 2

country-specific

country-

specific

HzCtlllLimTm

*

Tripping time for
underfrequency
level 2

0 ms …

1 000 000 ms

100 ms

HzCtlMin

*

Threshold value for
underfrequency
level 3

country-specific

country-

specific

HzCtlMinTm

*

Tripping time for
underfrequency
level 3

0 ms …

1 000 000 ms

100 ms

These parameters can only be changed if the installer password is entered.

Name

Description

Value/Range

Explanation

Default

value

FRTEna

*

These parameters are only visible after the installer password has been entered.

Enable dynamic grid
support

Off

Deactivated

On

On

Activated

FRTArGraNom

Scaling of the k-factor
for LVRT

1 … 10

country-

specific

EnaAid

*

Enable island grid
detection

Off

Deactivated

country-

specific

On

Activated

TrfVolExlHi

**

** 

These parameters can only be changed after the installer password has been entered.

Line-to-line voltage on
the overvoltage side
of the external
transformer

1 V… 70 000 V

20 000 V

TrfVolExlLo

**

Line-to-line voltage on
the undervoltage side
of the external
transformer

1 V … 40 000 V SC 500HE-20

270 V

SC 630HE-20

315 V

SC 720HE-20

324 V

SC 760HE-20

342 V

SC 800HE-20

360 V

Name

Description

Range

Explanation

Default

value