Electrical Connection

Installation Manual

SMC46-60A11-IA-en-81

37

• Off

The SMA Power Balancer is deactivated (default setting).
– If one of the inverters displays a device fault or a mains voltage fault, only the affected

inverter disconnects from the electricity grid and the other two inverters continue to feed in
at full power.

• PowerGuard

This setting can be selected if the entire PV plant only consists of three Sunny Mini Central
inverters and in the event of a malfunction, the unbalanced load should be limited to 4.6 kVA
over a 10-minute average.

– If one of the three inverters indicates a mains voltage fault or device fault and stops

feeding in, the other two inverters automatically limit their power over a 10 minute average
to 4.6 kVA.

Different unbalanced load limitation for SMC 6000A-11 inverters for Italy
The unbalanced load for SMC 6000A-11 inverters set to the national standard CEI 0-21
is limited to 6 kVA over a 10-minute average.