8 Output Assemblies (Drive Consumes)

24

YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual

‹

Speed and Torque Control Output - 22 (0x16)

‹

Extended Speed and Torque Control Output - 23 (0x17)

Speed Reference

Speed Command
Sets drive speed reference
Speed reference data:
Frequency reference / 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF
For example, when setting a reference of 1024 with a speed scale of 2
Speed reference data = 1024 / 2

2

= 256 = 0x0100

Unit depends on o1-03.

Output Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

22

0

Fault

Reset

Run

Fwd

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

4

Torque Reference/Torque Limit (Low Byte)

5

Torque Reference/Torque Limit (High Byte)

Name

Description

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Fault Reset

Fault Reset
0: No Fault Reset
1: Fault Reset

Speed Reference

Speed Command
Sets drive speed reference
Speed reference data:
Frequency reference / 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF
For example, when setting a reference of 1024 with a speed scale of 2
Speed reference data = 1024 / 2

2

= 256 = 0x0100

Unit depends on o1-03.

Torque Reference/Torque Limit

Torque Reference/Torque Limit
Sets the torque reference and torque limit in units of 0.1%.
Sets the torque reference when using torque control (d5-01 = 1).
Sets the torque limit when using speed control (d5-01 = 0).
The torque reference and torque limit are disabled when F6-06 = 0.

Output Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

23

0

Net
Ref

Net

Ctrl

Fault

Reset

Run
Rev

Run

Fwd

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

4

Torque Reference/Torque Limit (Low Byte)

5

Torque Reference/Torque Limit (High Byte)

Name

Description

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Run Rev

Reverse Run Command
0: Stop
1: Reverse Run