6 related parameters, Parameter f5-09, 6related parameters – Yaskawa 1000 Series Drive Option - Digital Output Installation User Manual

Page 23

Advertising
background image

YASKAWA ELECTRIC TOBP C730600 41F 1000-Series Option DO-A3 Installation Manual

23

6 Related Parameters

6

Related Parameters

The parameters outlined in the following sections are used to set up the unit for operation

with the option. Set parameters as needed. Parameter setting methods can be found in the

drive unit Instruction Manual.

Parameter F5-09

Set parameter F5-09 to select the option output mode.

Table 5

shows the changes in the output terminal contents according to the output mode set

in F5-09.

Table 5 F5-09 and Output Mode

Terminal

Block

Terminal

F5-09 = 0

Individual Output

(Default when Installed to

Drive)

F5-09 = 1

Binary Code Output

F5-09 = 2

Multi-Function Output

(Default when Installed

to Energy-Saving Unit)

TB1

M1-M2

Zero speed

During run

Determined by F5-07

M3-M4

Speed agree

Alarm (excluding bb)

Determined by F5-08

TB2

P1-PC

oC, GF (Overcurrent)

Binary code output
(Refer to

Table 6

.)

Determined by F5-01

P2-PC

ov (Overvoltage)

Determined by F5-02

P3-PC

oH2 (Unit overheat)
or oL2 (overload)

Determined by F5-03

P4-PC

Not used

Determined by F5-04

P5-PC

oS (Overspeed)

Zero speed

Determined by F5-05

P6-PC

oH, oH1 (Unit overheat)
or oL1 (Overload)

Speed agree

Determined by F5-06