5.5 Alarm Detection

u

Alarm Codes, Causes, and Possible Solutions

Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause of an alarm is removed,

the drive will return to the same status is was before the alarm occurred.
When an alarm has been triggered, the ALM light on the HOA keypad display blinks and the alarm code display flashes. If a

multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.

Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,

triggering alarms LT-1 through LT-3 (triggered only if H2-oo = 2F).

Table 5.11 Alarm Codes, Causes, and Possible Solutions

HOA Keypad Display

Minor Fault Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside of the acceptable setting range.

Cause

Possible Solutions

Station number is set outside the possible setting

range.

• Set parameter F6-10 to the proper value when using a CC-Link option.
• Set parameter F6-35 to the proper value when using a CANopen option.

HOA Keypad Display

Minor Fault Name

AUv

Power Supply Undervoltage
The input power supply voltage became equal to or lower than the Input Power Supply Undervoltage

Detection Level (L2-21).

200 V Class: Approximately 150 Vrms

400 V Class: Approximately 300 Vrms

HOA Keypad Display

Minor Fault Name

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

Cause

Possible Solutions

External baseblock signal was entered via one of

the multi-function input terminals (S1 to S8)

Check external sequence and baseblock signal input timing.

HOA Keypad Display

Minor Fault Name

bUS

Option Communication Error
• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.

Cause

Possible Solutions

Connection is broken or master controller stopped

communicating

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

Option is damaged

If there are no problems with the wiring and the fault continues to occur, replace the option.

The option is not properly connected to the drive

• The connector pins on the option are not properly lined up with the connector pins on the drive.
• Reinstall the option.

A data error occurred due to noise

• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
• Use recommended cables or some other type of shielded line. Ground the shield to the controller

side or on the input power side.

• Separate the wiring for communication devices from the drive input power lines.

HOA Keypad Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solutions

5.5 Alarm Detection

204

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual