VS-616/676 Series Option Instruction Manual: Isolated Analog Monitor Card AO-12B2

Page 11

PROGRAMMING PARAMETER SETTINGS

Note: Refer to “OUTPUT SIGNAL LEVEL SETTING” for 100% output signal level in output

Table 7: Programming Settings With VS-616G3

Terminal

Program

Parameter

Number

Set

Value

Output Contents

Output

Accuracy

TB1-1

Channel 1

Sn-28

1st/2nd

digit

00

Output frequency:

Max. frequency/100%

1.0%

01

Output current:

Inverter rated

voltage/100%

3.0%

TB1-2

Channel 2

Sn-28

1st/2nd

digit

10

Output voltage reference

Input voltage/100%

1.5%

11

DC voltage (V

PN

)

400V/100% (200Vclass)
800V/100% (400Vclass)

1.5%

Program the output terminal to the desired signal using the parameters in the following tables:

Table 7:

Programming settings with G3

Table 8:

Programming settings with H3

Table 9:

Programming settings with G5

Table 10: Programming settings with VG3 or VH3

Advertising