Yaskawa AC Drive Z1000 User Manual

Page 215

Advertising
background image

The main circuit capacitors are worn

• Check the maintenance time for the capacitors (U4-05).
• Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor,

contact Yaskawa or a Yaskawa representative.

Check for problems with the drive input power. If drive input power appears normal but the alarm

continues to occur, replace either the control board or the entire drive. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

SEr

Too Many Speed Search Restarts
The number of Speed Search restarts exceeded the value set to b3-19.

Cause

Possible Solution

Parameters related to Speed Search are set to the

wrong values

• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).

The motor is coasting in the opposite direction of

the Run command

Set b3-14 to 1 to enable Bi-Directional Speed Search.

HOA Keypad Display

Fault Name

STo

Motor Pull Out or Step Out Detection
Motor pull out or step out has occurred. Motor has exceeded its pull-out torque.

Cause

Possible Solution

Load is too heavy

• Increase the load inertia for PM motor (n8-55).
• Increase the pull-in current during accel/decel (n8-51).
• Reduce the load.
• Increase the motor or drive capacity.

Load inertia is too heavy

Increase the load inertia for PM motor (n8-55).

Acceleration and deceleration times are too short

• Increase the acceleration and deceleration times (C1-01 to C1-04).
• Increase the S-curve acceleration and deceleration times (C2-01).

Speed response is too slow

Increase the load inertia for PM motor (n8-55).

HOA Keypad Display

Fault Name

TdE

Time Data Error

Cause

Possible Solution

An error has occurred in the Real-Clock Time

function of the HOA keypad

Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your

nearest sales representative.

A communication error has occurred with the

Real-Clock Time function of the HOA keypad

HOA Keypad Display

Fault Name

TIM

Time Not Set

Cause

Possible Solution

The Real-Time Clock for the HOA keypad is not

set in parameter o4–17
• The drive is a new drive, first power-up

condition

• o4–17 was set to (2: Reset), by the user,

manually clearing the Real-Time Clock data.

Set the time for the HOA keypad. Parameter o4–17=1.
• For drive software PRG: 1012 and less, the drive will display the "TIM" alarm (Time Not Set)

whenever the Real time Clock is not set.

• For drive software PRG: 1013 and greater, the drive will display the "TIM" alarm (Time Not Set)

whenever the Real time Clock is not set . Additionally, at power up, if the "TIM" condition is

present, the drive will automatically switch to the time setting screen (o4–17=1) for 30 seconds to

prompt the user to set the Real-Time Clock.

The user did not set the Real Time Clock when

prompted following power-up.

Cycle power to the drive and set the Real Time Clock within 30 seconds of power-up, or set the clock

manually via parameter o4–17.

The HOA keypad battery is low or the battery has

been replaced

Replace the HOA keypad battery and set the Real-Time Clock.

An error has occurred in the Real-Time Clock

function of the HOA keypad

Replace the HOA keypad. For instructions on replacing the HOA keypad, contact Yaskawa or your

nearest sales representative.

HOA Keypad Display

Fault Name

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the

allowable time (L6-03).

5.4 Fault Detection

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

215

5

Troubleshooting

Advertising