Yaskawa Z1000 AC Drive User Manual

Z1000 ac drive quick start procedure, Page 1 of 2, Z1000 control wiring

Advertising
background image

Step

1

Z1000 Model

Identification and Mounting

Connect Motor and

Line Power

Step

2

Step

3

Z1000 Control Wiring

The following
procedure is a
supplement to
other
documentation
supplied with this
equipment and
will guide the user
in properly wiring
the Z1000 and
motor. It will also
show the user
how to configure
the Z1000 for a
Hand and Auto
operation.

DANGER!

Improper wiring
can and will cause

bodily harm as
well as damage to
the equipment.

When installing
the system be
sure to follow
good wiring
practices and all
applicable codes.
Ensure that the
mounting of the
various
components are
secure and that
the environment,
such as extreme
dampness, poor
ventilation etc. will
not cause system
degradation.

Please read this
cheat sheet and
the Z1000 User
Manual

(TOEP

C710616 45)

provided with the
Z1000 thoroughly
before attempting
any installation.

Page 1 of 2

WARNING DO NOT CONNECT ANY OF THE

FOLLOWING TERMINALS TO EARTH GROUND

+M

-M

-

+1

+3

Fig.1 & 2

below show the electrical connections for the input

power and motor terminals for various Z1000 models.

Select the

proper diagram for the model you are installing

(see Step 1).

WITH POWER OFF

make the appropriate connections.

Make sure to follow good wiring practices and all applicable
codes. Ensure that the equipment is grounded properly as
shown in fig. 1

DANGER;

LETHAL VOLTAGES ARE PRESENT- Before

applying power to the Z1000, ensure that the terminal cover
is fastened and all wiring connections are secure. After the
power has been turned OFF, wait at least five minutes until
the charge indicator extinguishes completely before touching
any wiring, circuit boards or components.

!

Make sure the Z1000 has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be at
least equal to or greater than the motor rated voltage.

DC Bus

terminals

location

varies by

model.

Use L1, L2, L3 for

3Ø Input Power

To change
direction of

motor rotation
swap any

two

of the

three

motor leads

(See Step 2)

Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 2_0011 - 2_0273, 4_0005 - 4_0302

Use L1, L2 for

1Ø Input Power

3Ø Induction

motor

Input

Protection

(Fuse or Circuit

Breaker)

L1

L2

L3

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to chassis

ground

*

Connect
frame to

ground

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

To change direction of motor

rotation swap any

two of the

three motor leads

(See Step 2)

Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2_0343 & Larger and 4_0361 & Larger

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis
ground

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

Use L1, L2 for

1Ø Input Power

*

BUS TERMINALS:
DO NOT CONNECT TO GROUND

*

To make sure you received the correct model, it is essential to
verify the Z1000 nameplate with your order and make sure the

Z1000 has the correct rating so it can be used with your motor.

Please check the nameplate information as shown in the

example below.

·

Check that the available power will meet the

input power

requirements.

·

Ensure that the

output power from the Z1000 is

compatible with the motor requirements.

Mounting the Z1000

·

In the case of systems with more than one Z1000, follow
the above procedure for each Z1000 and motor.

The mounting of the Z1000 is extremely important regarding
environment and accessibility. Depending on your system,
there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; the user is referred to the Z1000 User
Manual (Document No. TOEP C710616 45) received with the
Z1000,

Section 2.2 Mechanical Installation. Match the model

that you received and follow the procedure described in the
manual to ensure a safe and functional installation. In cases
where the system has more than one Z1000, refer to the
proper clearances required for adequate ventilation.

Please

pay particular attention to:

·

The clearances to be maintained around the enclosure
for adequate ventilation.

·

The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.

Removing and Attaching the Terminal Cover

Improper removal of the Z1000 terminal cover as well as
front cover can cause extensive damage to the Z1000. To
avoid damage to these items, please pay particular attention
to the Z1000 User Manual, Document No. TOEP C710616
45, Section 3.5, R

Removing and Attaching the Terminal

Cover.

NEMA 1

Open Chassis

Drive Model

Number

Input Power

Rating

Output Power

Rating

Serial

Number

UL File

Number

Drive Spec Number

Weight

Software

Version

This step shows how to setup the sequence and reference method of the Z1000. The sequence method determines how the Z1000
drive receives its start and stop command and the reference method determines how the speed of the motor is controlled. Make
sure all protective covers have been re-attached and power is turned on. D

DO NOT RUN THE MOTOR.

This section may require you to change one or more Z1000 parameters. Please refer to Step 5 for a detailed explanation on how to
change parameters.

SELECT START / STOP CONTROL METHOD

1.

Start / Stop Control from Digital Operator, use

See step 6
Hand / Auto Mode Operation

b1-02

2.

Start / Stop Control from external terminals (switch or relay contact)

Go to parameter
b1-02, set value to

( Factory Default)

NOTE: It is beyond the scope of this document to program the Z1000 drive for network communication control. Please refer to the
Z1000 Technical Manual, (Document No. SIEP C710616 45)

for this selection.

SELECT SPEED METHOD

b1-01

1.

Adjust motor speed / frequency from the Digital Operator

Go to parameter b1-01, set value to

2.

Adjust motor speed / frequency from external terminals (0 - 10V / 4 - 20mA Signal)

Go to parameter b1-01, set value to

(Factory Default)

+

To adjust frequency press from the operation screen and use / to change frequency and press .

+V

AC

A1

A2

FM

AM

AC

Potentiometer

2K Ohm

TB3 User Terminals

Wiring Diagram: 2-Wire Control

Forward

Reverse

Wiring Diagram: 3-Wire Control

Use for

momentary

contacts

Use for

maintained

contacts

(Set Parameter

A1-03 to 3330)

Link

Start

Switch

Reverse

Stop

Switch

Normally

Open

Normally

Closed

+V

AC

A1

A2

FM

AM

AC

0 ~ 10Vdc

+V

AC

A1

A2

FM

AM

AC

4 ~ 20mA

+

2 Wire / 4 ~ 20mA

Transducer

-

-

S1

S2

S3

S4

S5

S6

S7

SN

SC

SP

+P

FE

Link

S1

S2

S3

S4

S5

S6

S7

SN

SC

SP

+P

FE

TB1 User Terminals

FE

FE

Cable
Shield

Cable
Shield

+V

AC

A1

A2

FM

AM

AC

+

Brown or Red:
+Power (1)

Black: Output
4 – 20mA (2)

FE

Cable
Shield

SN

Install wire link
(AC-SN) when
using transducer.

+P

Z1000 AC Drive
Quick Start Procedure