2.1 Message Functions

2-7

2

Function Code (PARAM04)

The MEMOBUS function code to be sent is set. Refer to Table 2.4.

Note: 1.

−: cannot be set, OK: can be set

2. Only MW (MB) can be used as the sending/receiving register dur-

ing master operation. The MB, MW, IB, and IW registers can be
used respectively as the coil, holding register, input relay, and input
registers during slave operation.

Table 2.4 Function Codes

Function Code

Setting

00H

Unused

01H

Read coil status

OK

02H

Read input relay status

OK

03H

Read contents of holding register

OK

04H

Read contents of input register

OK

05H

Change status of single coil

OK

06H

Write into a single holding register

OK

07H

Unused

08H

Loop-back test

OK

09H

Read contents of holding register (expanded)

OK

0AH

Read contents of input register (expanded)

OK

0BH

Write into holding register (expanded)

OK

0CH

Unused

0DH

Discontinuous readout of holding register (expanded)

OK

0EH

Discontinuous write into holding register (expanded)

OK

0FH

Change status of a multiple coil

OK

10H

Write into a plurality of holding register

OK

11H to 20H

Unused

21H to 3FH

System reserved

40H to 4FH

System reserved

50H to

Unused