Bypass start-up procedure, Precautions for connected machinery – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 72

Advertising
background image

12.

Verify that all control wiring is run in separate conduit from motor or line power and route digital output wiring exceeding

24 V in conduit separate from other control wiring.

13.

Verify that the building automation system logic is ready for the start, stop, and speed command functions.

n

Precautions for Connected Machinery

WARNING! Sudden Movement Hazard. Clear all personnel from the drive, motor, and machine area before applying power. System may

start unexpectedly upon application of power, causing death or serious injury.

WARNING! Sudden Movement Hazard. Always check the operation of any fast stop circuits after they are wired. Fast stop circuits are

required to provide safe and quick shutdown of the drive. Prepare to initiate an emergency stop during the test run. Operating a drive with

untested emergency circuits could result in death or serious injury.

• The motor should come to a complete stop without problems.
• Connect the load and machinery to the motor.
• Fasten all installation screws properly and check that the motor and connected machinery are held in place.

u

Bypass Start-Up Procedure

After completing the steps in

Bypass Start-Up Preparation

, replace all P1000 Bypass and drive covers. Connect one end of

the HOA keypad cable to the Bypass control board A2 and one end to the door-mounted HOA keypad.

Step

Display/Result

1.

Remove any power source lockouts on the P1000 Bypass then turn the main input disconnect

handle clockwise to energize the P1000 Bypass.

Refer to Input Circuit Breaker on page

32

for details.

Use a multimeter to check all three-phase voltages for proper levels and balance and record

these levels for future reference.

During this sequence, the control logic will briefly (< 3 s) perform a self-test to ensure proper

operation.

YASKAWA

P1000

P1000 Bypass

Control

(VST000 )

2.

The keypad will now display the main startup screen showing that the P1000 Bypass is in

Drive mode and currently OFF. It also shows that the Bypass is in “AUTO” mode while

displaying the frequency reference.

DRV-OFF

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Freq Ref (AUTO)

LSEQ

LREF

RLY

DRV/BYP

3.

Press

one time to display the Monitor Menu.

All available drive and bypass monitors can be viewed from this menu.

Refer to Parameter

List on page 235

for a complete list of monitors.

DRV-OFF

U1-01= 60.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

Monitor Menu

LSEQ

LREF

RLY DRV/BYP

4.

Press

one time to display the Quick Settings Menu.

This is a condensed parameter set specifically selected for the initial drive start-up.

DRV-OFF

Quick Setting

DATA

HELP

5.

Press

one time to display the Programming Menu.

All available drive and bypass parameters can be accessed through this menu.

DRV-OFF

Programming

DATA

HELP

6.

Press

one time to display the Auto-Tuning Menu.

The Auto-Tuning function tunes the drive set-up to the characteristics of the motor to which

it is applied. Auto-Tuning is essential if bi-directional Speed Search is required and enabled

for the application.

DRV-OFF

Auto-Tuning

DATA

HELP

Auto

7.

Press

or

until the Quick Settings Menu screen is displayed.

DRV-OFF

Quick Setting

DATA

HELP

8.

Press

to access the Quick Settings parameters and adjust each parameter to the

appropriate setting for the application.

Refer to Quick Setting Parameters on page 68

for the list of parameters available in the

Quick Setting Menu.

DRV-OFF

Z1-07= 0 *0*

Operator

Spd Ref Sel

DATA

HOME

Checking the motor rotation in Drive and Bypass Modes.

4.5 Start-Up Procedure

72

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual