4.3 Simulation Mode

4.3.5 Output Signals in Simulation Mode

4-5

4

Operation Modes

( 2 ) AI Inputs

All AI inputs are treated as 0 (zero). Therefore, 0 (zero) will be always stored in the following monitoring parameters.

( 3 ) Latch Detection

The motion commands that use the latch function are disabled in simulation mode. Some operation examples are given
below.
<Example 1: Zero Point Return (ZRET) command>

···

The zero point return operation will never complete since the Latch Completed signal will never turn ON.

<Example 2: External Positioning (EX_POSING) command>

···

Executed as Positioning (POSING) command since no latch operation will be implemented.

<Example 3: Latch (LATCH) command>

···

Executed as Interpolation (INTERPOLATE) command since no latch operation will be implemented.

<Example 4: Modal Latch Request>

···

The latch operation will never be completed.

Refer to 11.4.1 Modal Latch Function on page 11-15

for information on modal latch.

( 4 ) Absolute Read Request

The Absolute Read Request will be ignored.

( 5 ) OT Processing

Disabled since DI inputs are disabled.

( 6 ) PG Disconnection Detection

The PG disconnection detection processing is masked.

4.3.5 Output Signals in Simulation Mode

Both DO and AO output 0 (zero) in simulation mode.

Register No.

Name

Range

Unit

IW

59

General-purpose AI monitor 1

−32768 to 32767

1 = 0.001 V

IW

5A

General-purpose AI monitor 2

−32768 to 32767

1 = 0.001 V