I & M Mark 67 (1/2” – 6”)

Installation & Maintenance Instructions for

Mark 67 Pressure Regulators

Warning: Jordan Valve pressure regulators must only be used, installed and repaired in accordance with these
Installation & Maintenance Instructions. Observe all applicable public and company codes and regulations. In the
event of leakage or other malfunction, call a qualified service person; continued operation may cause system failure
or a general hazard. Before servicing any valve, disconnect, shut off, or bypass all pressurized fluid. Before disas-
sembling a valve, be sure to release all spring tension.

Please read these instructions carefully!

Your Jordan Valve product will provide you with long,

trouble-free service if it is correctly installed and main-

tained. Spending a few minutes now reading these in-

structions can save hours of trouble and downtime later.

When making repairs, use only genuine Jordan Valve

parts, available for immediate shipment from the factory.

Ideal Installation

1.

To protect the valve from grit, scale, thread chips

and other foreign matter, ALL pipelines and piping

components should be blown out and thoroughly

cleaned before the installation process begins.

2.

Shutoff valves, pressure gauges and by-pass piping

should be installed as indicated in the diagram to

provide easier adjustment, operation, and testing.

3.

A line strainer should be installed on the inlet side

of the valve to protect it from grit, scale and other

foreign matter. A 0.033 perforated screen is usually

suitable for this purpose. Line strainers are avail-

able from Jordan Valve.

4.

For best control, 3’0” straight sections of pipe

should be installed on either side of the valve.

5.

In preparing threaded pipe connections, care

should be exercised to prevent pipe-sealing com-

pound from getting into pipelines. Pipe-sealing

compound should be used sparingly, leaving the

two end threads clean. Jordan uses, and recom-

mends, thread sealer Teflon ribbon.

6.

The flow arrow on the valve body must be pointed

in the direction of flow. Ideally, the valve should be

installed in the highest horizontal line of piping to

provide drainage for inlet and outlet piping, to pre-

vent water hammer, and to obtain faster response.

7.

If possible, install a relief valve downstream from

the valve. Set at 15 psi above the control point of

the valve.

8.

In hot vapor lines, upstream and downstream pip-

ing near the valve should be insulated to minimize

condensation.

9.

In gas service, expand the outlet piping at least

one pipe size if the control pressure (downstream)

is 25% of the inlet pressure or less. A standard

tapered expander connected to the outlet of the

valve is recommended.

10. Where surges are severe, a piping accumulator is

recommended.

11. On steam control applications, install a steam trap

with sufficient capacity to drain the coil or condens-

er. Be sure to have a good fall to the trap, and no

backpressure. Best control is maintained if the coil

or condenser is kept dry.

Control Line

A control line must be installed as follows:

1.

Connect one end of a 3/8” tubing to the fitting un-

der the diaphragm.

2.

Connect the other end in a straight run of pipe 3 to

5 feet downstream of the valve.

3.

DO NOT locate the control line tap in an elbow,

swage or other changes in configuration of the

pipeline where turbulence or abnormal velocities

may occur.

4.

DO NOT locate the control line tap in vessel, such

as a deaerator located immediately downstream of

the valve. Locate the tap in the pipeline leading to

the vessel.

5.

The control line should be sloped away from the

valve.

6.

Install a shutoff valve (not a needle valve) in the

control line.

Main Steam Line

Condensate Return Line

1. Shut off Valve

2. Jordan Regulator

3. Strainer and Drain Valve

4. Pressure Gauge

5. Relief Valve

6. Steam Trap

1

6

3

1

1

2

1

5

4