Authorised electrician

7.2.2 Connecting the PV generator

Connect the PV generator on the left in the connection area (Figure 13 on page 21). Use the provided M16 cable

fittings. A maximum of two strings can be connected. For this reason, a DC string fuse can be dispensed with.

DANGER

Risk of fatal injury due to contact voltages.
Removing the cables from the terminals without first disconnecting the PV generator from the

device can cause serious damage to health or damage to the system.

During installation: Electrically disconnect the DC positive and DC negative from the protective

earth (PE).

Completely de-energise the system (AC home power grid, AC circuit breaker, residual current circuit

breaker, DC isolator switch)

Disconnect the battery system from the PV generator using the integrated DC isolator switch.

Remove DC plug connectors.

NOTE

In accordance with IEC 61730 Class A, connected PV modules must be dimensioned

for the DC system voltage provided, and at least for the value of the AC grid voltage.

7.2.2.1 Before connecting

Ensure that there is no ground fault
1. Determine the DC voltage between the

protective earth (PE) and the positive cable of the PV generator, and between the

protective earth (PE) and the negative cable of the PV generator.

If stable voltages can be measured, there is a ground fault in the DC generator or its wiring. The ratio between the

measured voltages gives an indication as to the location of this fault.
2. Rectify any faults before taking further measurements.
3. Determine the electrical resistance between the

protective earth (PE) and the positive cable of the PV generator, and between the

protective earth (PE) and the negative cable of the PV generator.

In addition, ensure that the PV generator has a total insulation resistance of more than 2.0 MOhm, since the

inverter will not feed in if the insulation resistance is too low.
4. Rectify any faults before connecting the DC generator.

7.2.2.2 Connecting the PV generator

DANGER

Risk of fatal injury due to electric shock
Severe injury or death will result if the live connections are touched. When there is solar radiation, DC

voltage will be present at the open ends of the DC cables.

Do not touch the exposed ends of the cables.

Avoid short circuits.