Magnum Energy ME-125F User Manual

Page 2

Advertising
background image

ME-125F and ME-200F Instruction Sheet

© 2011 Magnum Energy, Inc.

Conductor Gauge

Current Capacity*

Recommended Fuse

#1 AWG/42.39 mm²

190

200**

#4 AWG/21.14 mm²

125

125

* - Current capacity based on 75° C cable rating in free air @ 30° C (86° F).

** - The next larger standard size overcurrent device may be used if the
de-rated cable ampacity falls between the standard overcurrent devices
found in the NEC.

~

5.00" (12.7 cm)

~

4.50" (11.43 cm)

1.25"

(3.17 cm)

.75"

(1.9 cm)

5/16 – 18 bolt w/ Hex nut (x2)

Requires 9/16" wrench

Figure 1, Small Fuse Block Dimensions

WARNING: During installation, incorrect stacking of the fuse
block hardware can create a highly resistive connection that
generates heat. DO NOT place anything (i.e., washers)
between the fuse and either battery cable lug
as this can
cause the fuse to overheat and blow open, resulting in a partial
melting of the fuse holder and cover. Before stacking, refer to
Figure 2.

Figure 2, Small Fuse Block Hardware Stacking

Fuse

Battery Cable

Lugs

Flat Washers

Lock Washers

Hex Nuts

Table 1, Fuse Selection

Advertising