Dealer installation instructions – Beam Electrolux HEPA Air Filter Central User Manual

Page 4

Advertising
background image

4

Dealer Installation Instructions

Forced air handler/furnace systems:

The HEPA system should be installed as a bypass system, with part of the
return ducted into the HEPA system. The filtered air is then rerouted back
into the return air, and continues through the system to be heated/cooled.

Preparation:

Here are some things to consider as you decide where to install the
HEPA system.

Location:

• Make sure there is room to open the HEPA filter access panel for filter

changes/inspections.

• Keep the HEPA system in a location where you can still access the air

handler/furnace filter.

• Keep the HEPAsystem away from possible water damage.
• Vibration pads will reduce vibration for installations where the unit is placed

on the floor.

• Install HEPA System on floor or suspended platform. If the unit is suspended,

screws must not penetrate through the cabinet. Make sure that you have
the proper chains/straps/joists and equipment to keep unit secure. Intake
(Marked as ‘Air In’ on unit):

• Intake ducts should be installed upstream of any humidifiers and be

installed on the main return.

• Intake duct should be installed at least 6 ft. away from the outflow duct on

the main return. Outflow (Marked as ‘Clean Air Out’ on unit):

• Outflow duct should be installed as close to the air handler/furnace inlet as

possible but not directly into the return air elbow of the main return.

• If the unit is being installed independently of any other system, room diffusers

are recommended to help distribute airflow evenly in the occupied space.

Ducting:

• If HEPA system is installed where inlet and outflow collars face down, metal

elbows must be connected to both inlet and outflow collars.

• Each connection must be sealed with aluminum tape or mastic, including

all take offs.

• Installed duct runs should be as straight as possible (if the duct runs are

too long, reduced CFM may result).

• If duct is exposed to unconditioned air, externally insulated flex duct is highly

recommended.

• Externally insulated flex duct can also be used for noise reduction purposes.
• For best indoor air quality, do not use ductboard or fiberglass inside of ducts.

Electricity:

• The unit must be plugged into a grounded 20V, 60Hz outlet.

Required Materials for Installation of Unit:
Items for 350

Flex or rigid duct (length as required)

8” round & 6” round

Takeoffs

One 8” & One 6”

Items for 675

Flex or rigid duct (length as required)

0” round & 8” round

Takeoffs

One 0” & One 8”

All Models

Aluminum tape or mastic as required

Misc. hanging materials - field provided

NOTE: Be sure to review ‘Rules for Safe Installation and Operation’ on page 
of this document before start-up of this unit.

A

A

B

B

Air Handler/

Furnace

Air

Handler/Furnace

Filter

HEPA System

Distance between
A and B should
be 6' to 16' for
best results

Distance between A and B should
be 6' to 16' for best results

Typical Return to Return Application

For homes with upflow forced air handler/furnace systems.( Air handler/furnace
is shown in a typical basement.)

Typical Return to Return Application

For homes with horizontal forced air handler/furnace systems. (Air handler/
furnace is shown in an typical attic.

NOTE: This filtration system is an ADDITIONAL filter, and does NOT replace the existing air handler/furnace system filter.

Advertising