8

Micro Motion

®

Series 3000 Transmitters and Discrete Controllers

Environmental specifications

Power supply

EMI effects

All Series 3000 devices Meet EMC directive 89/336/EEC per EN 61326 Industrial, and all Series
3000 devices conform to NAMUR NE21 (June 1997).

Ambient temperature effect

On analog outputs

±0.005% of span per °C

Ambient temperature limits

(1)

(1) If exposed to direct sunlight, the ambient temperature can be expected to rise by an additional 50 °F (10 °C).

Operating

–4 to +140 °F

–20 to +60 °C

Storage

–40 to +158 °F

–40 to +70 °C

Temperature accuracy

Models 3500 and 3700

±1.0 °C ±0.5% of reading in °C

Temperature repeatability

Models 3500 and 3700

±0.2 °C

Humidity limits

5 to 95% relative humidity, non-condensing at 140 °F (60 °C)

Vibration limits

Per IEC 68-2-6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g

AC power supply

Model 3300

85 to 265 VAC

50/60 Hz, 15 VA

0.25 A maximum at 85 VAC, 0.12 A maximum at 265 VAC

IEC 127-3/4 fuse, 0.63 A time-delay

Complies with European low-voltage directive 2006/95/EC per IEC 61010-1

Installation (Overvoltage) Category II, Pollution Degree 2

Models 3350, 3500,
and 3700

85 to 265 VAC

50/60 Hz, 30 VA

0.33 A maximum at 85 VAC, 0.15 A maximum at 265 VAC

IEC 127-3/4 fuse, 0.63 A time-delay

Complies with European low-voltage directive 2006/95/EC per IEC 61010-1

Installation (Overvoltage) Category II, Pollution Degree 2

DC power supply

Model 3300

18 to 30 VDC

7 watts typical, 14 watts maximum

IEC 127-3/4 fuse, 1.6 A time-delay

Models 3350, 3500,
and 3700

18 to 30 VDC

18 watts typical, 25 watts maximum

IEC 127-3/4 fuse, 1.6 A time-delay