Figure 47 gate board viewing slot locations, Gate board viewing slot locations – Emerson Liebert Static Transfer Switch User Manual

Page 76

Advertising
background image

Operating Instructions for the Touch Screen Interface

68

Figure 47 Gate board viewing slot locations

If the Color Graphical Display is not available, you can still use the following bypass procedures,

ignore the steps to check the display and check the LEDs.
If your system contains the LED display, see 14.2.3 - Maintenance Bypass.

GREEN LEDS ON THE

GATE DRIVER BOARD

ARE VIEWABLE

THROUGH THIS SLOT

INDICATE THAT THE

STS IS ON SOURCE 1

GREEN LEDS ON THE

GATE DRIVER BOARD

ARE VIEWABLE THROUGH

THIS SLOT INDICATE THAT

THE STS IS ON SOURCE 1

Viewing Slot for

the Source 1

Gate Drive Board

Touch Screen

GREEN LEDS ON THE

GATE DRIVER BOARD ARE

VIEWABLE THROUGH THIS

SLOT INDICATE THAT THE

STS IS ON SOURCE 2

Viewing Slot for

the Source 2

Gate Drive

Board