Emerson Liebert Remote Monitoring Panel User Manual

Page 19

Advertising
background image

Operation

15

Current Record Window
Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions

that have been resolved. Use “page” (F1) and up / down arrow to read the events.
For a complete history log, refer to the Records tab of the Menu and Data Window.
Refer to Table 13 for a complete list of supported status messages.

Battery

Battery voltage (V)

Battery bus voltage

Battery current (A)

Battery bus current

Battery temperature (°C)

Battery temperature °C

Remain Time Min.

Battery run time remaining

Battery boost charging

Battery is boost charging

Battery float charging

Battery is float charging

Battery disconnected

Battery is not connected

Records

(history log)

Displays all records in the history log

Language

(choices for text displayed) User may select any of 12 languages for LCD text.

Settings

Display contrast

Adjust the LCD display contrast

Date format set *

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

Date & time *

Set the date and time

Comm1 baud rate *

Communication baud rate setting for IntelliSlot 1

Comm2 baud rate *

Communication baud rate setting for IntelliSlot 2

Comm3 baud rate *

Communication baud rate setting for IntelliSlot 3

Communication address *

This setting is applicable to RS485 communication mode

Communication mode *

Communication Mode Setting

Callback times *

When IntelliSlot 1 Communication mode is Modem, this parameter sets

the number of times a number is redialed to send an alarm notification.

Phone No.1 *

When IntelliSlot 1 Communication mode is Modem, this is the first phone

number to be dialed (to send an alarm notification).

Phone No.2 *

When IntelliSlot 1 Communication mode is Modem, this is the second

phone number to be dialed (to send an alarm notification).

Phone No.3 *

When IntelliSlot 1 Communication mode is Modem, this is the third phone

number to be dialed (to send an alarm notification).

Command password *

User can modify the command password.

Command

(start/stop

battery &

system

tests)

Battery maintenance test * This test performs a partial discharge of the battery to obtain a rough

estimate of the battery capacity. Load must be between 20% and 100%.

Battery capacity test *

This test performs a full discharge of the battery to obtain a precise

measure of the battery capacity. Load must be between 20% and 100%.

System test *

This is a self-test of the UPS. When the user activates this function, a

popup window appears about 5 seconds later to show the results.

Stop testing *

Manually stops a battery maintenance test, battery capacity test or system

test.

Freshening Charge *

This command will allow a temporary Equalize charge for the batteries.

This charge is configurable for 1 to 36 hours

Stop Freshening Charge *

Manually stop a Freshening Charge

Modem Auto-answer

enable *

Manually enable the auto-answer function of modem.

Version

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and

software display board.

UPS model

Provides UPS model information—for example, 400V-50Hz.

* Visible from the RMP, but the control is available at UPS only.