Installation – Essick Air ECR 7200 User Manual

Page 9

Advertising
background image

9

IMPORTANT

NOTE: When checking amperage with the ampmeter,

all louvers must be in place in the cooler,
otherwise incorrect setting of the drive pulley
will occur.

MOTOR PULLEY ADJUSTMENT

NOTE: ALL DUCT CONNECTED COOLERS MUST
BE ADJUSTED.

Long or small air ducts have excessive air resistance
which decreases air output and motor amperage. You may
compensate for this by adjusting the motor pulley. Use a
clamp type ampmeter to check the motor amperage.

1. Check amperage at the white lead in the wiring box.

2. If the amperage is less than the motor nameplate

amperage, loosen the pulley pitch adjustment screw,
turn in the pulley 1/2 turn, tighten the screw and
recheck the amperes. Repeat as necessary to bring
the amperage to the nameplate rating.

3. If the amperage is too high, turn out the pulley as

required.

4. Adjust the belt tension as required. (See page 13)

INSTALLATION

FIGURE 13

STARTUP INSPECTION

Before starting the cooler, make sure all installations and
adjustments are correct. Be sure that:

• Cooler is level and duct is sealed.

• Cabinet is securely fastened to the mount.

• Cooler is grounded. Electrical connections are secure.

• Blower wheel does not rub against housing.

• Water supply is turned on.

• Water line is connected securely and fittings and

crossover tube grommets do not leak.

• Float is adjusted for proper water level.

• Pulley alignment is OK. Belt tension is OK (See page 13).

• Pads are correctly installed (See page 13).

• Blower and both pad motors are plugged into receptacles.

• All louver clips are snapped tight.

STARTUP CHECK LIST

To check out the installation follow this startup proce-
dure. Set the control to each position and check opera-
tion per the following chart. Be sure to open windows or
vents.

OPERATION WITH ESSICK SWITCH ECR-5

(Five Position)

Blower

Pad

Switch

Motor

Motors

Off

Off

Off

Low Vent

Low

Off

High Vent

High

Off

Low Cool

Low

On

High Cool

High

On

OPERATION WITH ESSICK SWITCH ECR-7

(Seven Position)

Blower

Pad

Switch

Motor

Motors

Off

Off

Off

Low Vent

Low

Off

High Vent

High

Off

Minimum

Cool — Low

Low

One On

Minimum

Cool — High

High

One On

Maximum

Cool — Low

Low

Both On

Maximum

Cool — High

High

Both On