EMI S2H User Manual

Page 2

Advertising
background image

Made in rome, new York, usa

s2Ha High Capacity Condensing unit

s2H dIMEnsIons and sPECIFICatIons

notE: All EMI products are subject to ongoing development programs so design and

specifications may change without notice.

s2H ELECtrICaL sPECIFICatIons

ModEL

(1)

VoLts/HZ/PHasE

Fan

CoMPrEssor 1 CoMPrEssor 2 totaL

aMPs

MIn. CIr.

aMPs

(2)

HaCr

BrKr

rLa

HP

rLa

Lra

rLa

Lra

9900

208-230/60/1

1.8

0.33

3.4

23

3.4

23

8.6

9.5

15

2200

208-230/60/1

1.8

0.33

4.3

27

4.3

27

10.4

11.5

15

9200

208-230/60/1

1.8

0.33

3.4

23

4.3

27

9.5

10.6

15

(1) Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)

(2) Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.

1/2” Diameter Lag Holes

4.63”

4.63”

28.74”

12.44”

3.00”

s2H PIPInG sPECIFICatIons

sound data

sHIPPInG

WEIGHt

Model#

Line sizes

Liquid

suction

dBa

Lbs.

9900

1/4”

1/2”

64

159

2200

1/4”

1/2”

65

197

9200

1/4”

1/2”

65

187

44”

38”

15”

Electrical

connections

Front of unit

Easy access interconnects

on back of unit

Advertising