System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

Page 13 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

List of Parts

List GA: Distribution Cabinet

(20) GMT Fuse System Positions with
Split Bus

Features

♦ Single Voltage Distribution (-48V)
♦ Maximum Capacity: Input: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.

Total Distribution: 30A per bus, 60A total @ +65°C
Battery Recharge Current: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.
Battery Terminals as Remote Feed: 103A @ +40°C; 95A @ 50°C; 50A @ +65°C.

♦ (20) Mounting Positions for Alarm-Type Load Distribution Fuses, (10) per bus.
♦ Accepts GMT-Type Fuses (1/4A to 15A).
♦ Includes (20) dummy fuses equipped with safety fuse covers.
♦ Provides local and external fuse alarm.
See

Distribution Cabinet Electrical Connection Locations and Dimensions

.

Restrictions

Maximum distribution fuse size: 15A

Maximum size wire each fuse position accepts is 14 AWG.

Input is cable-fed only.

Maximum size wire input terminals accept is (1) 2 AWG per polarity.

No load or battery shunts are provided.

Ordering Notes

1) Order fuses, as required, per Tables