Thermostat location (sg models) – Empire Products GWT-25-2 User Manual

Page 11

Advertising
background image

12425-7-0406

Page 11

THERMOSTAT LOCATION (SG MODELS)

CAUTION — Do not run wire behind flanges of Header Plate

or in any location where it might be damaged.
Millivolt wall thermostats are specially designed for use on self-

generating systems. They should never be used on line or low

voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside

wall away from the furnace but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of milli-

volts.
Proper operation depends on a good pilot flame. The flame must

cover the top of the thermopile. Cleaning of the pilot orifice and

burner may be required due to spiders.
System Check (Figure 7)

A millivolt meter is required to check the system. Millivolt

readings should be:
• Across the thermopile terminals, 400-450 millivolts with

thermostat OFF.

• Across the thermopile terminals, 150-250 millivolts with

thermostat ON.

• Across the thermostat wires at the valve, less than 30 millivolts

with thermostat ON.

• Across the thermostat wires at the thermostat, less than 5

millivolts with thermostat ON. (Dirty pilot or low pressure

will reduce readings.)

Connect thermostat wires to gas valve as shown in Figure 7.

Figure 7

Advertising